What Is a Copper Busbar and Why Copper?
A copper busbar is a thick strip of conductive copper used to carry and distribute large currents inside switchgear, transformers, battery packs and industrial panels. Copper is preferred over aluminium for one simple reason: it conducts roughly 60% more current for the same cross-section, resists corrosion well, and allows tighter, more reliable bolted joints. For space-constrained cabinets and high-reliability systems, that efficiency often outweighs the higher material cost.




Grade Selection: C11000 vs C10100
Most busbars are made from C11000 electrolytic tough pitch copper with a minimum 99.90% purity and about 100% IACS conductivity. It offers the best balance of performance and price. Where the application demands lower oxygen content and slightly higher conductivity – for example vacuum or specialty electronics – C10100 oxygen-free copper is used instead. For the overwhelming majority of switchgear, panel and battery applications, C11000 is the correct and most economical specification.
Ampacity Reference for Rectangular Busbar
| Width x Thickness (mm) | Approx. Cross-Section (mm²) | Typical Current (A) | Common Application |
|---|---|---|---|
| 20 x 3 | 60 | 250–300 | Control panels, small distribution |
| 30 x 5 | 150 | 550–650 | General switchgear |
| 50 x 5 | 250 | 800–950 | Main distribution boards |
| 60 x 10 | 600 | 1600–2000 | EV battery packs, heavy power |
Ampacity values depend on ambient temperature, airflow, mounting method and allowable temperature rise. Always confirm the final sizing against your local standard before production.
Sizing and Thickness
Busbar dimensions are driven by three forces: current rating, mechanical stiffness and available cabinet space. Thicker bars handle more current and resist vibration better, while wider bars give more surface area for bolted connections. Tolerances are critical – a busbar that is 0.2 mm oversized can be impossible to insert, and one that is undersized creates contact resistance and hot spots. Specify width, thickness and edge radius precisely, and require a dimensional inspection report.
Surface Finish: Bare, Tinned or Plated
- Bare copper: highest conductivity, lowest cost, best for controlled indoor environments.
- Tin-plated: added corrosion resistance and stable contact resistance – the standard for humid or coastal installations.
- Nickel / silver plated: for high-temperature or high-reliability joints in specialty equipment.
Typical Applications
- Low-voltage switchgear and control panels
- EV battery packs and charging systems
- Transformers and power distribution units
- Renewable energy inverters and UPS systems
Quality Checks Before You Buy
- Confirm grade and conductivity (IACS) against the mill certificate.
- Verify thickness and width tolerance with measured samples.
- Inspect edges for burrs and cracks from the slitting process.
- Require a flatness check so bars seat correctly in the cabinet.
Why Buy Busbar from SYLAITH
WUXI SYLAITH SPECIAL STEEL CO., LIMITED (brand SYLAITH) supplies C11000 and C10100 copper busbar in custom widths and thicknesses, bare or tin-plated, cut and edged to your drawings. We support both prototype and volume orders with stable quality, documented inspection and reliable export service, helping panel builders and equipment makers keep production lines running without interruption.
Request a Quote
Send your busbar drawing, grade, plating and quantity to sales2@slssteel.com for a specification review, MOQ, lead time and price basis within one working day.